Interior and exterior security managed 24/7 by permanently assigned staff of Wackenhut guard
Zoned access throughout Data Cente
Biometric hand scanner requires ID card access and hand geometry measurements
Customer IDC access and contacts managed via Siebel
Current government-issued picture ID required
ID badge and biometric hand scan to man trap with badge reader
Second hand scans to gain access to raised floor Biometric scanner captures 3D measurements of hand
Security cameras
Multiple 360 degree cameras with 10x zoom
More than 100 fixed cameras
High speed recorders with DV cassette tapes
Hard drives to eliminate down time for tape swaps and over recording
Minimum 30 day tape storage Generator power * Backup power
Multiple CAT Diesel 20 megawatt generators
Minimum 24 hour fuel storage
Agreements with two major carriers to provide additional diesel fuel
Generators assumes building load within 20 seconds
Generators are tested on weekly basis under load
Tanks are kept at least 80% full at all times
Two utility feeds from independent substations
Diverse paths to the building
Feeds to building are encased in concrete
Fed from two independent substations
Separate transformers fed from both utility sources for redundancy
HVAC chiller systems
Hosting space HVAC system includes (16) AHUs and (16) ACCUs manufactured by Trane
AHUs are DX type and located in the mechanical mezzanine; the ACCUs are located on the roof
There is adequate capacity to withstand a HVAC unit failure or an entire bus failure Cooling is provided by both overhead and under floor air
HVAC systems have wetted media fo r humidification,VFDs for each supply fan, exhaust fans to control building pressure, and economizers to utilize cool outside air
Separate Dectron outside air handling units provide conditioned air for the hosting space
UPS Room cooling is provided by Trane RTUs in a N+1 configuration
Node room cooling is provided by Liebert DX CRAC units in a N+1 configuration
Network facilities - Main Node Room
Multiple fiber providers for diversity - provides diversity and redundancy
Each vendor can deliver additional bandwidth capacity with minimal turn-around time
Can be delivered using existing ‘lit’ fiber
Fiber pathways into the Data Center are truly diverse
Fiber enters building in steel conduit from multiple points in the building
|